Advance Surge Suppressor logo





Voltage Signal Surge Suppressor Two Wire

Two Wire
Voltage Signal Surge Protector


Type: TSP-WG6-xxV-1A-0y

Where:

xx = Compliance Voltage
y = 2 - Polarized Voltage
y = 4 - Non-Polarized Voltage

Features:

Application: Transient surge protectors provide common and differential mode protection for toll booths, drawbridges, street light controllers and railroad crossing gates/signals. Electronic equipment is extremely susceptible to transient voltages and surge currents due to its relatively fragile semiconductor construction. A surge protector is a cost effective method of ensuring that equipment will have maximum life.

Voltage Signal Surge Suppressor Two Wire connection diagram

Function:The module has a protected SIGNAL and POWER side which is connected to the data acquisition system input and power supply. It also has a LINE side which is connected to the transmission wire. The EARTH connection of the modules must be terminated to earth by low impedance heavy gauge wire.


Description:

The TSP-WG6-xxV-1A-0y is a transient protection module which provides over-voltage and surge current protection for 2 wire voltage signal circuits. The module provides two stages of protection for the power path and three stages of protection for the signal path. Internally, the module has 100% redundancy to safeguard the system and prevent nuisance failures. This series of modules is for systems using power, signal and return wires.

Technical Specifications:

Operating Voltage:
(See Note)
+(+/-)10V +(+/-)24V +(+/-)60V +(+/-)130V
Signal Power Signal Power Signal Power Signal Power
LINE Side Max. Input Voltage 11.1VDC 11.1VDC 28.2VDC 28.2VDC 70VDC 70VDC 145VDC 145VDC
Over-Voltage Level PROTECTED Side Suppression Begins 12.4VDC TRANZORB 16.5VRMS MOV 16.5VRMS
MOV
31.4VDC TRANZORB 35VRMS
MOV
35VRMS
MOV
77.9VDC TRANZORB 85VRMS
MOV
85VRMS
MOV
162VDC TRANZORB 165VRMS
MOV
165VRMS
MOV
Maximum Clamp Volts for Max. Transients on Line 18.2VDC TRANZORB 36VRMS
MOV
36VRMS
MOV
45.7VDC TRANZORB 77VRMS
MOV
77VRMS
MOV
113VDC TRANZORB 165VRMS
MOV
165VRMS
MOV
234VDC TRANZORB 300VRMS
MOV
300VRMS
MOV
Surge Current: 8/20µSec Pulse
2mSec Pulse
2000A
10 Joules
2000A
10 Joules
4000A
44 Joules
4000A
44 Joules
13000A
66 Joules
13000A
66 Joules
13000A
120 Joules
13000A
120 Joules
Series Resistance 15 Ohms 5 Ohms 15 Ohms 5 Ohms 15 Ohms 5 Ohms 15 Ohms 5 Ohms
Resistance to Earth:
Max. Over-Voltage
Operating Voltage

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm
Suppression Threshold Voltage Derating (mV/°C) 11.0 11.0 30.0 30.0 86.0 86.0 188.0 188.0

(NOTE: Polarized = +VDC; Non-Polarized = +/-VDC or AC RMS)

Packaging and Dimensions:
WEG 6 terminal modular housing, #12 to #22 AWG terminals.
Size: 60.6 mm x 90.5 mm x 22.5 mm (2.39" x 3.56" x 0.89") (W x H x D excluding DIN Rail)
Operating Conditions:
-40 to +85 °C (-40 to 185°F), 0 to 93% Relative Humidity
Ordering Part Number:
+ 10V ..... TSP-WG6-10V-1A-02
+ 24V ..... TSP-WG6-24V-1A-02
+ 60V ..... TSP-WG6-60V-1A-02
+ 130V ... TSP-WG6-130V-1A-02
+/-10V .... TSP-WG6-10V-1A-04
+/-24V .... TSP-WG6-24V-1A-04
+/-60V .... TSP-WG6-60V-1A-04
+/-130V... TSP-WG6-130V-1A-04
Variations available by special order.

Specifications are subject to change without notice.

To place an order or to get more information, please call us:

Phone:
Fax:

General Inquiries:
Sales:

(905)602-9270
(905)602-9279

info@advancesurgesuppressor.com
sales@advancesurgesuppressor.com

We accept: VISAMasterCard


Return to Surge Suppressor Main Page