AC Surge Protector

AC Surge Suppressors


Type: TSP-WG6-xxxVAC-10A-01

Where:

xxx=Input Voltage

Features:

Application: Transient surge protectors provide common and differential mode protection for toll booths, drawbridges, street light controllers and railroad crossing gates/signals. Electronic equipment is extremely susceptible to transient voltages and surge currents due to its relatively fragile semiconductor construction. A surge protector is a cost effective method of ensuring that equipment will have maximum life.

Function: The module has a PROTECTED SIDE - LIVE, NEUTRAL and EARTH which is connected to the equipment supply lines requiring protection. It also has a LINE SIDE - LIVE, NEUTRAL and EARTH which is connected to the AC supply power conductors. The EARTH connection of the modules must be terminated to earth by low impedance heavy gauge wire.

AC Surge Suppressors connection diagram

Description:
The TSP-WG6-xxxVAC-10A-01 is a three stage transient protection module which provides over-voltage and surge current protection for single phase supply lines. The first stage provides transient rise time reduction. The second stage provides the primary transient voltage clamping and a LED circuit to indicate that the device is still fully functional. This second stage will be removed from the circuit well before the useful life of the device has expired. This will provide ample time for the device to be replaced ensuring continued protection of the connected equipment. The third stage is the most rugged and provides the bulk of the transient protection.

Technical Specifications: All voltages are RMS unless otherwise specified. All specifications typical at nominal input voltage and 25°C unless otherwise specified.

Operating Voltage 18VAC 24VAC 48VAC 120VAC 240VAC
LINE Side Max. Input Voltage:

PROTECTED Side Voltage Level Suppression Begins:
Stage Two
Stage Three

Max. Clamp Volts for Max.
Transients on Line:
Stage Two
Stage Three

Surge Current:
8/20µ Sec Pulse
L to N
L to E
N to E
2m Sec Pulse
L to N
L to E
N to E

Response Time

Resistance to Earth Max. Over-Voltage:
Operating Voltage:
20VAC


30V
35V



65V
77V



9000A
4000A
4000A

94J
44J
44J

<5 nSec

0.01 Ohm
>1 MOhm
30VAC


42V
50V



93V
110V



9000A
4000A
4000A

139J
66J
66J

<5 nSec

0.01 Ohm
>1 MOhm
60VAC


90V
110V



165V
200V



30500A
13000A
13000A

177J
80J
80J

<5 nSec

0.01 Ohm
>1 MOhm
130VAC


175V
195V



340V
360V



36500A
16000A
16000A

346J
156J
156J

<5 nSec

0.01 Ohm
>1 MOhm
270VAC


390V
440V



710V
775V



28500A
16000A
8000A

590J
346J
173J

<5nSec

0.01 Ohm
>1 MOhm
Packaging & Dimensions:
WEG 6 terminal modular housing, #12 to #22 AWG terminals.
Size: 60.6 mm x 90.5 mm x 22.5 mm (2.39" x 3.56" x 0.89") (W x H x D excluding DIN Rail)
Operating Conditions:
-40 to +85°C (-40 to 185°F), 0 to 93% Relative Humidity
Ordering Part Number: With Indicator
18VAC 10A ... TSP-WG6-18VAC-10A-01
24VAC 10A ... TSP-WG6-24VAC-10A-01
48VAC 10A ... TSP-WG6-48VAC-10A-01
120VAC 10A ...TSP-WG6-120VAC-10A-01
240VAC 10A ...TSP-WG6-240VAC-10A-01

Variations available by special order.

Specifications are subject to change without notice.