Advance Surge Suppressor logo





Current Loop Surge Suppressor One Wire

One Wire 4 to 20 mA
Current Loop Surge Protector


Type: TSP-WG4-20MA-xxxV-01 (Unipolar)
Type: TSP-WG4-20MA-xxxV-03 (Bipolar)


Where: xxx = Compliance Voltage

Features:

Application: Transient surge protectors provide common and differential mode protection for toll booths, drawbridges, street light controllers and railroad crossing gates/signals. Electronic equipment is extremely susceptible to transient voltages and surge currents due to its relatively fragile semiconductor construction. A surge protector is a cost effective method of ensuring that equipment will have maximum life.

Function: The module has a PROTECTED side which is connected to the transducer output or to the data acquisition system input and a LINE side which is connected to the transmission wire. The EARTH connection of the modules must be terminated to earth by low impedance heavy gauge wire.

Current Loop Surge Suppressor One Wire connection diagram

Description:
The transient surge protector features a three stage protection mechanism which provides over-voltage and surge current protection for 1 wire +/- 4 to 20 mA current loops. Internally, the module has 100% redundancy to safeguard the system and prevent nuisance failures. This series of modules is for systems using a separate power supply for the transducer and the data acquisition system.

Technical Specifications: All specifications typical at nominal input voltage and 25°C unless otherwise specified.

Operating Voltage: (See note) +(+/-) 15V + (+/-)30V +(+/-) 60V +(+/-) 200V
LINE Side Max. Input Voltage 17.1VDC 33.3VDC 70.1VDC 256VDC
Over-Voltage Level PROTECTED Side Suppression Begins:
Stage Two TRANZORB
Stage Three MOV


Maximum Clamp Volts for Maximum Transients on Line:
Stage Two TRANZORB
Stage Three MOV

19VDC
20VRMS


27.7VDC
43VRMS

37.1VDC
42VRMS


53.9VDC
93VRMS

77.9VDC
89VRMS


113VDC
165VRMS

285VDC
330VRMS


414VDC
595VRMS
Surge Current:
8/20µSec Pulse
2mSec Pulse

4000A
24 Joules

4000A
52 Joules

13000A
66 Joules

8000A
130 Joules
Series Resistance 15 Ohms 15 Ohms 15 Ohms 15 Ohms
Resistance To Earth:
Max Over-Voltage
Operating Voltage

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm

0.01 Ohm
>1 MOhm
Suppression Threshold Voltage Derating: (mV/°C) 19.0 36.0 86.0 315.0

(NOTE: Unipolar = +VDC; Bipolar = +/-VDC or AC RMS)

Packaging and Dimensions:
WEG 4 terminal modular housing, #12 to #22 AWG terminals.
Size: 60.6 mm x 90.5 mm x 16.5 mm (2.39" x 3.56" x 0.65") (W x H x D excluding DIN Rail)
Operating Conditions:
-40 to +85 °C (-40 to 185°F), 0 to 93% Relative Humidity
Ordering Part Number:
+15V ..... TSP-WG4-20MA-15V-01 (Unipolar)
+30V ..... TSP-WG4-20MA-30V-01
+60V ..... TSP-WG4-20MA-60V-01
+200V ... TSP-WG4-20MA-200V-01
± 15V .... TSP-WG4-20MA-15V-03 (Bipolar)
± 30V .... TSP-WG4-20MA-30V-03
± 60V .... TSP-WG4-20MA-60V-03
± 200V .. TSP-WG4-20MA-200V-03
Variations are available by special order.

Specifications are subject to change without notice.

To place an order or to get more information, please call us:

Phone:
Fax:

General Inquiries:
Sales:

(905)602-9270
(905)602-9279

info@advancesurgesuppressor.com
sales@advancesurgesuppressor.com

We accept: VISAMasterCard